Is the County covering the Quality Assurance field and lab testing leaving Quality Control on the awarded prime correct? (RFC 46281 submitted 2/23/2022)
Yes. Response date: 03/07/2022
Drawing No. ISD SHERIFF E3
ISD Sheet E3 - Fiber vaults 1 & 2 - not shown on electrical, site plan, or ISD drawings. Are they New? by us? Existing? (RFC 46397 submitted 3/2/2022)
See Addendum 2. Response date: 03/07/2022
Drawing No. E1.0 - E20; Project Manual Section No. 26000
There appear to be 2 sets of electrical drawings included in the plan set with an overlap in scope. Are both sets of electrical drawings valid? (RFC 46399 submitted 3/2/2022)
Yes, both sets of drawings are valid. The Internal Services Division sheets provide supplemental details for the Data and UPS equipment and layout and identify owner supplied/contractor installed equipment and devices. Response date: 03/07/2022
Drawing No. A2.2
On sheet A2.2 – door ST119 & ST120 are shown as new and they are also on the door schedule. On sheet A2.4 – door ST101 and ST114 are also shown along with the above. On the door schedule notes 2 reads, " for doors shown on the plan but not listed on the door schedule, see "area 2 substation storage building" drawings." Can you please confirm under bid package 2, the contractor is responsible for door ST119 & ST120 only? (RFC 46426 submitted 3/3/2022)
Yes, ST119 and ST120 are the only doors in this contract. Response date: 03/07/2022
Can you confirm the storage building slab is existing? If not, can you please provide foundation plan along with slab section as required? (RFC 46427 submitted 3/3/2022)
The building slab is existing. Response date: 03/07/2022
Drawing No. A2.6
On sheet A2.6 detail A1 calls for keynote 8 in room SS113. There is no keynote 8 under keynote legend. Can you provide description for this keynote? (RFC 46428 submitted 3/3/2022)
See Addendum 2. Response date: 03/16/2022
Drawing No. A2.6
On sheet A2.6 – Detail A1 & A13 calls for "new chase". It says expansion of existing electrical room in notice to bidders, can you provide the existing layout for the electrical room so we can determine any demolition that needs to occur? (RFC 46429 submitted 3/3/2022)
On sheet A2.6, Details A1 & A13, the chase is incorrectly labeled as "new chase." This is an existing chase. With the exception of removal of temporary roof joist brace, no demolition of the existing electrical room structure will be required. This is clarified in Addendum 2. Response date: 03/16/2022
Can you provide location and quantity of the EV charging stations for additive bid #2? (RFC 46430 submitted 3/3/2022)
This is clarified in Addendum #2. There will be a total of 7 EV Charging Stations. The stations will be Owner Furnished Contractor Installed. Response date: 03/07/2022
Will the Area 2 substation bid package #1 be completed before bid package #2 starts? (RFC 46431 submitted 3/3/2022)
No. Response date: 03/07/2022
Will the paving be completed in the area east of the courtyard (A/C & Gen Yard)? (RFC 46432 submitted 3/3/2022)
All paving will be completed with current Phase 1 construction. Response date: 03/07/2022
Will the bid package #1 be occupied prior to bid package #2 start? (RFC 46433 submitted 3/3/2022)
No. Response date: 03/16/2022
Will contractors have access to view the site? (RFC 46435 submitted 3/3/2022)
Yes, but it will require an appointment with County Staff. Phase 1 construction is currently in progress. Potential bidders are welcome to drive by, but access onto the site will require an appointment. Response date: 03/07/2022
No. Potential bidders are welcome to drive by, but bidders will not have access to view the site. The initially posted response was incorrect. Response date: 3/14/2022
Potential bidders are welcome to drive by, but access to the site will be by appointment only as Phase 1 construction is currently in progress. Please contact LaRue Goossen at 559-862-5441 to schedule a visit.
Drawing No. A1.2; Project Manual Section No. 26 50 00
Detail J13/A1.2 shows lighting at the carports, and refers to the electrical drawing by note. There is nothing shown for pathways or lighting on the electrical drawings. Please provide additional details. (RFC 46443 submitted 3/3/2022)
See Addendum 2. Response date: 03/07/2022
Drawing No. E15
Drawing E15 shows a clean agent fire suppression system to be provided by and installed by contractor. There is no specification section for this work. The electrical requirements for this system do not appear to be provided for on the electrical drawings. Please provide additional details and a specification for this system. (RFC 46445 submitted 3/3/2022)
IT Data Center clean agent fire suppression system shall be a contractor provided design-build deferred submittal. Contractor shall submit plans to Fresno Fire for separate permit. A copy of the permit shall be delivered to the Architect for processing with Fresno County Development Services. See Addendum 2. Response date: 03/16/2022
Drawing No. A2.4
On sheet A2.4 detail J7 finish schedule – Since the framing is existing, can you please confirm the interior plywood walls and ceiling are also existing in existing electrical room? Is the painting of the plywood part of bid package #2? (RFC 46452 submitted 3/4/2022)
Interior plywood walls and ceiling in the electrical room are existing and painted as part of Bid Package #1. Response date: 03/16/2022
Drawing No. A5.1; Specification No. 07 46 19 Steel Siding
Can you please provide a manufacturer for this material. The specification is ambiguous regarding embossing, QA requirements, finishes and trim. (RFC 46499 submitted 3/8/2022)
Wall panels are 48" wide x 24 galvanized sheet metal siding. No embossing will be required. See Addendum 2. Response date: 03/16/2022
Drawing No. M3.0 Specification No. 20 00 00; 23 08 00; 00 52 13
Per specification section 00 52 13 the contract duration is 60 calendar days. Per the plans and cited General Mechanical and HVAC sections the HVAC equipment is supplied and installed by the contractor. If the equipment is not OFCI and scheduled for delivery early in the project, the lead times associated with it subsequent to approved submittals will far exceed the contract duration. We are currently seeing lead times on CRAC equipment in excess of 40 weeks. Please confirm the equipment is CFCI, and there is no provision already in place for the Owner to provide it according to the construction schedule. (RFC 46512 submitted 3/9/2022)
Construction timeline has been revised and clarified in Addendum 2 to account for equipment lead times for Contractor Supplied equipment as well as Owner Furnished equipment. Response date: 03/17/2022
Drawing No. A0.3
Sheet A0.3 Fire Protection Notes call for the installation of a wet fire sprinkler system, for which there is no specification. Please confirm this is part of bid package 1, and should not be included in this bid package. (RFC 46513 submitted 3/9/2022)
Wet system will not be required. See Addendum 2. Response date: 03/16/2022
Specification No. 84113
Please confirm the interior storefront will be Delegated Design and require engineer calculations. (RFC 46519 submitted 3/9/2022)
Interior storefront will not be Delegated Design and will not require engineer calculations. See Specification Section in Addendum 2. Response date: 03/16/2022
In previously asked question (RFC 46432), it states all paving will be completed with phase1 and phase one will not be completed when phase 2 starts (RFC 46431). Will the parking pavement be performed after all parking lot conduits are installed? Should we figure on saw cutting and demo of pavement for running conduits to canopies, EV stations and at yard? (RFC 46533 submitted 3/10/2022)
Pavement sections is clarified in Addendum 2. Response date: 03/17/2022
Drawing No. A2.4 & E19
On sheet E19, it shows a 8" housekeeping pad inside the data center. On sheet A2.4 keynote 1 also mentions 8" pad, but it refers to detail N1/A5.1. Can you please clarify if we are to provide 8" pad or per the detail shown on N1/A5.1? (RFC 46556 submitted 3/11/2022) Sheet E19 will be omitted.
This is clarified in Addendum 2. Response date: 03/17/2022
Drawing No. A0.2
On sheet A0.2, General Notes – Can you confirm note 26 will be completed by phase 1 contractor? (RFC 46578 submitted 3/14/2022)
General Note 26 is revised in Addendum 2. Response date: 03/17/2022
Can you please confirm if final cleaning of the whole project/building is part of Phase 1 contractor scope (Exception to Phase 2 scope)? (RFC 46579 submitted 3/14/2022)
Final clean for this contract will be limited to areas of work as depicted in the drawings and any additional areas utilized by the contractor for material storage, staging, etc. This is clarified in Addendum 2. Response date: 03/17/2022
Drawing No. E1
The Internal Services Department plan set single-line diagram is showing pretty much everything on this sheet as contractor provided and contractor installed. Is this correct? Some of the information on this single line diagram conflicts with the other single line diagram (sheet E1.1). For example the internal services department plans show the diesel generator as furnished and installed by contractor, which is incorrect according to sheet E1.1 single line diagram. The information on these 2 sheets contradict each other. Please advise. (RFC 46925 submitted 4/6/2022)
The generator is Owner provided and Contractor installed. Response date: 04/07/2022
Drawing No. E3
Please clarify whether or not the conduit sleeves entering the data center are new or existing as shown on sheet E3 of the Internal Services Division drawings. (RFC 46960 submitted 4/8/2022)
The conduit sleeves entering the Data Center are existing conduits. Response date: 04/11/2022