In This Section
Drawing No: A10.11
1. Detail A1-D/A10.11 is referenced several times (Ex. J14/1-A6.2 and A14,E14/1-A6.1) however This detail does not appear to be occurring on sheet A10.11, can you please provide this detail or direct to correct detail reference? 2. Regarding the ½" fire treated plywood substrate on this project; please confirm that ½" fire treated ply substrate is only occurring on this project where wall lines on the arch floor plans are specifically called out as being either wall types 15A, 15B, 15C or 15D per wall type schedule on A1/A10.11. 3. What is the fastening requirement for this ½" fire treated ply? 4. Is this ½" fire treated ply being supplied by the pre-engineered building supplier? 5. Where is detail A5/A10.12 occurring, please advise?